Key takeaways
- The HVAC system meaning is heating, ventilation and air conditioning. Designing Buildings says it can be used in buildings to “Maintain internal air quality. Regulate internal temperatures. Regulate internal humidity.”
- An HVAC system is made of parts such as air handling units, chillers, fan coil units, ductwork, filters and refrigerant circuits. This page defines each one briefly and links to the guide that covers it, within our commercial air conditioning section.
- Only some parts carry legal duties: refrigerant circuits (F-gas), air conditioning systems over 12 kW in England and Wales (inspection), and cooling towers and evaporative condensers (legionella and notification). The table near the end sets them out.
- Every part with refrigerant carries a CO2 equivalent: tonnes = kg x GWP / 1,000. Ten kilograms of R32 is 6.75 tonnes; ten kilograms of R410A is 20.88 tonnes.
What does “HVAC system” mean?
Designing Buildings says “‘HVAC’ refers to Heating Ventilation and Air Conditioning”, used in buildings to maintain air quality, temperature and humidity. A system can be centralised or local to the space it serves, integrated (one system doing all three jobs) or a combination of separate systems, such as mechanical ventilation with radiators and local comfort cooling units (Designing Buildings, last edited 8 September 2026). For the term itself and the UK duties, see what HVAC is; for how the parts work together, see how an HVAC system works. This page is a reference list of the parts.
The parts, A to Z
Air curtain
A fan over a door. Daikin says the airflow of its Biddle air curtains “acts as a curtain that reduces heat loss and eliminates turbulence”. Its efficiency percentages state no test method. See shop air conditioning.
Air handling unit (AHU)
Designing Buildings says air handling units “typically comprise an insulated box” that may include filter housings, a fan or blower, heating and cooling elements, dehumidification equipment, sound attenuators and dampers. An AHU is the part that treats air in a ducted system. See HVAC ductwork.
Building management system (BMS)
Designing Buildings says “HVAC may be controlled by a building management system to maximise occupant comfort and minimise energy consumption.” It is the control layer, not a piece of plant.
Cassette
A ceiling-mounted indoor unit. Daikin’s Round Flow cassette has “360° air discharge”. See cassette air conditioning units.
Chiller
“Chillers remove heat from a liquid through a refrigeration cycle” (Designing Buildings). The chilled water is piped to air handling units or fan coil units. Air-cooled chillers reject heat to the outside air; water-cooled chillers are “generally suited to large systems and require connection to cooling towers”.
Condensing unit
The outdoor unit of a split system. See condensing units explained. A chiller cools water; a condensing unit works with refrigerant piped to indoor units.
Cooling tower and evaporative condenser
Water-based heat rejection used with water-cooled plant. HSE says “If you have a cooling tower or evaporative condenser, you should put in place appropriate measures” to prevent or control legionella. See the table below.
Ductwork
BESA’s DW/144 is its specification for sheet metal ductwork, covering “commercial and industrial air distribution systems operating under normal conditions up to 70 °C”, with pressure classes A to D. A standard is not a law; ask what a contractor builds to. See HVAC ductwork.
Fan coil unit (FCU)
Designing Buildings, quoting BSRIA, describes a device “mounted in the ceiling void or floor mounted often at the perimeter of a building” with a fan, coils and a filter, supplied with hot and chilled water, as “two pipe (either heating or cooling) or four pipe (both heating and cooling)”. See fan coil units.
Filter
Freudenberg, a filter maker, says ISO 16890 uses four groups: “ISO ePM1”, “ISO ePM2,5”, “ISO ePM10” and “ISO coarse”, with at least 50% needed for the respective group, and that “A 1:1 comparison between filter class according to EN 779 and filter class according to ISO 16890 is not possible.” See HVAC filters.
Heat pump
A system that moves heat; the same refrigeration cycle can heat or cool. See air-to-air heat pumps.
Heat recovery
Two different things carry this name. Designing Buildings describes heat recovery ventilation (HRV) as recovering “heat from extract air” to pre-heat incoming fresh air. In VRF, heat recovery moves heat from zones needing cooling to zones needing heating. See VRF air conditioning.
Refrigerant
The fluid that carries heat round a refrigeration circuit. R32 has a global warming potential (GWP) of 675 (Annex I of the F-gas Regulation as it applies in Great Britain); the US EPA’s table gives 2,088 for R410A. See air conditioning refrigerants and R32.
VRF or VRV
One outdoor unit serving several indoor units. VRV is Daikin’s name; Designing Buildings says VRF was first developed by Daikin as “variable refrigerant volume” (VRV). See VRF air conditioning.
Which parts carry legal duties?
This is general information, not legal advice. Each row names the nation where we confirmed it.
| Part | Duty | Source |
|---|---|---|
| Any refrigerant circuit (air conditioning, heat pump, chiller) | Great Britain: qualifications to install, service, check for leaks, recover gas and decommission; a company servicing for others “must be certified by an approved body” | GOV.UK F-gas pages |
| Refrigerant circuit holding 5 tonnes CO2 equivalent or more | Great Britain: leak checks at least every 12 months, or 24 with a leak detection system; every 6 months from 50 tonnes, or 12 with one; 500 tonnes or more must have a leak detection system and is then checked at least every 6 months | Our rules data; GOV.UK |
| Air conditioning system with an effective rated output of more than 12 kW | England and Wales: inspection at intervals not exceeding five years; see TM44 inspections | EPB Regulations 2012, regulations 17 and 18 |
| Cooling tower or evaporative condenser | HSE says to put in place measures to prevent or control legionella, and regulation 3 requires notification to the local authority; the nation each covers was not shown on the pages we opened | HSE; Notification of Cooling Towers and Evaporative Condensers Regulations 1992, regulation 3 |
| Mechanical ventilation plant | England, Wales and Scotland: ventilation by “a sufficient quantity of fresh or purified air” | Workplace Regulations 1992, regulation 6 |
| Ductwork, filters, air curtains, fan coil units | We found no specific legal duty for these on the pages we opened; standards such as DW/144 and ISO 16890 are not law | BESA; Freudenberg |
What is the CO2 equivalent of a refrigerant charge?
Tonnes CO2e = kg x GWP / 1,000. Our arithmetic: 10 kg of R32 is 10 x 675 / 1,000 = 6.75 tonnes, over the 5 tonne line at which annual leak checks start. 10 kg of R410A is 10 x 2,088 / 1,000 = 20.88 tonnes, also in the 5 to under 50 tonne band. The R410A figure is the US EPA’s, used here for illustration only; we did not check the figure the GB F-gas Regulation uses for this blend, so ask your engineer for the system’s CO2 equivalent. Read the charge from the rating plate. See F-gas rules.
Frequently asked questions
What does HVAC system mean?
Heating, ventilation and air conditioning: the plant that controls a building’s air quality, temperature and humidity, according to Designing Buildings.
What are the main components of an HVAC system?
Air handling units, chillers, fan coil units, ductwork, filters, refrigerant circuits (splits, cassettes and VRF), cooling towers where fitted, and controls or a building management system.
What is an AHU?
An air handling unit: an insulated box that may hold filters, a fan, heating and cooling elements, dehumidification equipment, sound attenuators and dampers.
What is the difference between a chiller and a condensing unit?
A chiller cools a liquid, such as water, that is piped to air handling or fan coil units. A condensing unit is the outdoor part of a split system; refrigerant is piped to the indoor units. See condensing units explained.
What is a BMS?
A building management system: Designing Buildings says it may control HVAC “to maximise occupant comfort and minimise energy consumption”.
Which HVAC parts need legal inspections?
Air conditioning systems over 12 kW in England and Wales need a TM44 inspection; refrigerant circuits need leak checks from 5 tonnes CO2 equivalent in Great Britain; cooling towers and evaporative condensers need legionella control. See the table above.
Sources
- Designing Buildings: HVAC (last edited 8 September 2026) (checked 25 November 2026)
- Designing Buildings: Fan coil unit (last edited 4 August 2022) (checked 25 November 2026)
- Designing Buildings: Chiller (last edited 16 December 2025) (checked 25 November 2026)
- Designing Buildings: Variable refrigerant flow VRF (last edited 3 August 2021) (checked 25 November 2026)
- Daikin UK: Biddle air curtains (checked 25 November 2026)
- Daikin UK: Round Flow FCAG-B (checked 25 November 2026)
- HSE: Evaporative cooling systems (updated 14 January 2026) (checked 25 November 2026)
- legislation.gov.uk: Notification of Cooling Towers and Evaporative Condensers Regulations 1992, regulation 3 (checked 25 November 2026)
- BESA: Sheet metal ductwork standards (11 November 2025) (checked 25 November 2026)
- Freudenberg Filtration Technologies: ISO 16890 (checked 25 November 2026)
- GOV.UK: Checking F gas equipment for leaks (checked 25 November 2026)
- GOV.UK: Qualifications to work with F gas (updated 3 March 2026) (checked 25 November 2026)
- GOV.UK: Certification for companies working on equipment containing F gas (checked 25 November 2026)
- legislation.gov.uk: F-gas Regulation (EU) No 517/2014 as it applies in Great Britain, Annex I (checked 25 November 2026)
- US EPA: Technology Transitions GWP reference table (checked 25 November 2026)
- GOV.UK: Air conditioning inspections for buildings, a guide (updated 5 November 2026) (checked 25 November 2026)
- legislation.gov.uk: EPB Regulations 2012, Part 4 (checked 25 November 2026)
- legislation.gov.uk: Workplace (Health, Safety and Welfare) Regulations 1992, regulation 6 (checked 25 November 2026)