Key takeaways
- How does a HVAC system work? In a commercial building (see our commercial air conditioning guide) it moves heat out, brings fresh air in, filters it, and is switched and adjusted by thermostats or a building management system.
- Cooling is carried round a building by refrigerant (splits and VRF), by chilled water (chillers feeding fan coil units and air handling units) or by air through ducts.
- Cooling does not equal ventilation, on our reading: a unit that recirculates room air does not on its own supply fresh air, and HSE says systems that recirculate air should be designed with fresh-air inlets that “should be kept open”.
- Our working: a 5 kW cassette delivering its rated cooling at Daikin’s seasonal efficiency of 6.93 uses about 0.72 kW of electricity and sends about 5.72 kW of heat outdoors.
The short answer
An HVAC system (heating, ventilation and air conditioning; see what HVAC means) moves heat from where you do not want it to where it does no harm, supplies fresh air, cleans that air with filters, and keeps all of it under control. The heat is moved either by refrigerant, by chilled water or both. Which method a building uses decides what kind of equipment sits in the ceiling void and on the roof. This is the whole-building view; the individual parts are in HVAC system meaning and components, and the section home is commercial air conditioning.
Step 1: moving heat with refrigerant
Daikin UK describes the refrigerant cycle in four steps. The compressor takes refrigerant from a low-pressure gas to a high-pressure gas, heating it. The condenser lets the hot, pressurised gas give off its heat to the surrounding air, so it cools into a high-pressure liquid. The expansion valve lowers the pressure, which drops the temperature below that of the space being cooled. The evaporator lets the cold liquid absorb warmth from indoor air and turn back into gas, which returns to the compressor. Daikin says a heat pump applies “this same four-step process in reverse”. Our guide to how air conditioning works and the condensing unit glossary entry go into more detail. The point for a building: this moves heat, it does not make cold.
Step 2: carrying the cooling round the building
Refrigerant to each room: split and VRF
In a split or multi split system, refrigerant pipes run from an outdoor unit to one or more indoor units. Designing Buildings says VRF “circulates refrigerant between an outdoor unit and several indoor units”. See VRF air conditioning explained.
Water to each room: chillers, fan coils and air handling units
Designing Buildings says “Chillers remove heat from a liquid through a refrigeration cycle”, and that chillers mainly provide comfort cooling for HVAC systems. Air-cooled chillers reject heat to outside air by circulating it through the condenser; water-cooled chillers are generally suited to large systems and need a connection to cooling towers. Fan coil units can be supplied with chilled and hot water from central plant. A fan coil unit is “a fan, a heating coil, a cooling coil and an air filter housed in a metal casing”, fed by chilled or hot water (Designing Buildings, quoting BSRIA). That is why a commercial system can have water pipes in the ceiling. See fan coil units explained.
Air through ducts: air handling units and ductwork
An air handling unit is an insulated box that may hold filter racks, a fan, heating and cooling elements, dehumidification, sound attenuators and dampers. Connected to ductwork, one system can heat, ventilate and cool. BESA says its DW/144 specification covers sheet metal ductwork for commercial and industrial air distribution up to 70 °C. See HVAC ductwork.
Step 3: fresh air and filtration
This is general information, not legal advice. Regulation 6 of the Workplace (Health, Safety and Welfare) Regulations 1992 (England, Wales and Scotland) says every enclosed workplace must be ventilated “by a sufficient quantity of fresh or purified air”. HSE says “The fresh-air supply rate should not normally fall below 5 to 8 litres per second, per occupant”, which it takes from its Approved Code of Practice and guidance. HSE’s improving-ventilation page says systems that recirculate air “should therefore be designed with fresh-air inlets, which should be kept open”, and that mechanical systems should be “maintained in line with manufacturers’ instructions”.
Filters are graded under ISO 16890. Freudenberg, a filter maker, says the groups are ISO ePM1, ePM2.5 and ePM10 (a filter must separate at least 50% of the matching particles) and ISO coarse; the test covers particles from 0.3 to 10 micrometres, and “A 1:1 comparison between filter class according to EN 779 and filter class according to ISO 16890 is not possible.” See HVAC filters.
Step 4: heating with the same system
A heat pump runs the cycle in reverse and heats. In VRF, Designing Buildings says two-pipe systems “can provide either cooling or heating (heat pump systems) to all of the zones”, while three-pipe heat recovery systems can heat some zones while cooling others, with heat from zones needing cooling used to heat those needing heating. Daikin’s VRV 5 Heat Recovery uses a “3-pipe heat recovery design”. For air-to-air units see how an air-to-air heat pump works.
Step 5: controls
Controls set zones, timers and set points. Daikin’s hotel page describes key card systems that “automatically communicate with your Daikin units to turn off the air conditioning or heating” when guests leave or windows open. Larger buildings link plant to a building management system; we did not open a source that describes one, so we say no more about how they work.
Where the heat ends up
Outdoor units reject heat to the air outside. Water-cooled chillers reject it through cooling towers. HSE names “cooling tower and evaporative condensers” among the most common sources of legionella and does not name air conditioning; it says “If you have a cooling tower or evaporative condenser, you should put in place appropriate measures to prevent or control the” risk. Under regulation 3 of the Notification of Cooling Towers and Evaporative Condensers Regulations 1992, a person in control of premises must ensure no notifiable device is on them unless it has been notified in writing to the local authority, on HSE’s approved form.
Which parts are in which system
| System | Moves heat by | Fresh air? | Room-end equipment |
|---|---|---|---|
| Split or multi split | Refrigerant | No (recirculates) | Wall, cassette or ducted indoor unit |
| VRF | Refrigerant | Only with a separate ventilation system | Indoor units per zone |
| Chiller with fan coils | Chilled water | Only if paired with an air handling unit | Fan coil units |
| Air handling unit with ducts | Chilled water or refrigerant coil | Yes, if designed to | Ducts, grilles, diffusers |
The fresh air column is our summary of the descriptions above.
Our working: where the heat goes
Energy is conserved, so the heat sent outdoors equals the heat taken from the building plus the electricity used. Daikin’s table for the Round Flow FCAG60B with RZAG50B gives 5 kW nominal cooling and a SEER of 6.93, which is about 0.72 kW of electricity for 5 kW of cooling (5 / 6.93). So about 5 + 0.72 = 5.72 kW leaves through the outdoor unit while it delivers 5 kW of cooling. That is a simplified, one-point sum, not a measurement.
Air changes: Broughton’s MCe9.0 portable moves 1,080 m3 an hour through its evaporator, and Broughton gives a “typical cooled area” of 220 m3. 1,080 / 220 = 4.9 air changes an hour, our arithmetic. That air is recirculated room air, not fresh air.
How to brief an installer
- Say which rooms need cooling, heating and fresh air, and give hours of use.
- Ask how heat will be moved (refrigerant, chilled water or both) and where the outdoor plant goes.
- Ask who supplies fresh air and how filters will be maintained.
- Ask for the controls specification and the F-gas details for the refrigerant.
Frequently asked questions
How does an HVAC system cool a building?
It moves heat out of the building with refrigerant or with chilled water produced by a chiller, and releases it outdoors.
Does an HVAC system bring in fresh air?
Only if it is built to. HSE says recirculating systems should be designed with fresh-air inlets that are kept open; a split unit on its own recirculates room air.
What is the difference between a chiller and an air conditioner?
A chiller cools water that is piped to coils, while a split air conditioner cools the air in a room directly with refrigerant coils. Designing Buildings says chillers “remove heat from a liquid”.
How does one system heat and cool at the same time?
Heat recovery VRF moves heat from zones that need cooling to zones that need heating, according to Designing Buildings.
What does a thermostat or BMS do?
A thermostat switches heating or cooling to a set temperature. We did not open a source on how a building management system works, so we give no definition.
Why does a commercial system have water pipes?
Chilled and hot water reach fan coil units and air handling units by pipework from central boilers and chillers.
Sources
- Daikin UK: The refrigerant cycle, what is it? (checked 25 November 2026)
- Designing Buildings: Variable refrigerant flow VRF (last edited 3 August 2021) (checked 25 November 2026)
- Designing Buildings: Chiller (last edited 16 December 2025) (checked 25 November 2026)
- Designing Buildings: Fan coil unit (last edited 4 August 2022) (checked 25 November 2026)
- Designing Buildings: HVAC (last edited 8 September 2026) (checked 25 November 2026)
- BESA: Sheet metal ductwork standards (11 November 2025) (checked 25 November 2026)
- legislation.gov.uk: Workplace Regulations 1992, regulation 6 (checked 25 November 2026)
- HSE: Assessing the risk of poor ventilation (checked 25 November 2026)
- HSE: How to improve ventilation (checked 25 November 2026)
- Freudenberg Filtration Technologies: ISO 16890 (checked 25 November 2026)
- Daikin UK: VRV (checked 25 November 2026)
- Daikin UK: Hotels (checked 25 November 2026)
- HSE: Legionella, workplace risks (checked 25 November 2026)
- HSE: Evaporative cooling systems (updated 14 January 2026) (checked 25 November 2026)
- legislation.gov.uk: Notification of Cooling Towers and Evaporative Condensers Regulations 1992, regulation 3 (checked 25 November 2026)
- Daikin UK: FCAG-B / RZAG-B technical details (checked 25 November 2026)
- Broughton: MCe9.0 specification sheet (May 2023) (checked 14 November 2026, as recorded in our product file; the PDF could not be re-read on 25 November 2026)
Products on this page
Daikin
Round Flow cassette FCAG60BVEB with Sky Air RZAG50B5V1B outdoor unit
5 kW cooling · SEER 6.93
No current UK price found
Broughton
Mighty Cool MCe9.0 Low GWP Portable Monoblock Air Conditioner (230V)
9 kW cooling · 65 dB
No current UK price found
Figures from the maker or retailer listing. Cost an hour is our own, at the price cap of 26.32p a kWh.