VRF Air Conditioning Explained: Heat Pump and Heat Recovery

By Editorial team. Updated 28 November 2026. Facts checked 25 November 2026.

Key takeaways

  • VRF air conditioning (variable refrigerant flow) is a system of one outdoor unit serving several indoor units, each in its own zone. It is one of the system types in our commercial air conditioning guide.
  • VRV is Daikin’s name for the same idea: Designing Buildings says VRF was first developed by Daikin under the trade name “variable refrigerant volume” (VRV), and Daikin’s page is headed “Daikin VRV, invented by us”.
  • A heat pump VRF system heats or cools all its zones at once; a heat recovery system can heat some zones while cooling others. Makers’ saving claims for heat recovery (Mitsubishi Electric says “up to 30%”) have no stated baseline.
  • Leak checks depend on the refrigerant’s CO2 equivalent: with R32 the annual check starts at 7.41 kg, and twice-yearly checks at 74.07 kg. We found no published VRF price on 25 November 2026.

What is VRF air conditioning?

Designing Buildings defines it as “a system for the heating, ventilation and air conditioning (HVAC) of buildings”. In practice, one outdoor unit is joined by refrigerant pipes to several indoor units, and the flow of refrigerant to each is varied to match what that zone needs. Mitsubishi Electric UK says its City Multi VRF outdoor units “can be connected to up to 50 indoor units” and suit medium to large buildings. Our guide to multi split air conditioning covers the smaller, home-scale version of the same idea; Mitsubishi’s home-scale range is in our Mitsubishi multi split systems page.

Is VRV different from VRF?

Not in principle. Designing Buildings says VRF “was first developed by Daikin Industries in Japan, under the trade name ‘variable refrigerant volume’ (VRV)”. Daikin UK’s page is headed “Daikin VRV, invented by us”. Other makers say VRF; Mitsubishi Electric’s range is called City Multi. See Daikin’s commercial ranges and Mitsubishi Electric air conditioners. We say VRF unless we are quoting Daikin.

What is the difference between heat pump and heat recovery VRF?

Designing Buildings says “Two pipe systems can provide either cooling or heating (heat pump systems) to all of the zones”. Three-pipe systems use “heat recovery enabling heat from zones requiring cooling to be used to heat zones that require heating”, and the page says they have a greater capital cost.

  • Daikin: its VRV 5 Heat Recovery has a “Highly effective 3-pipe heat recovery design” and offers “Simultaneous cooling and heating”.
  • Mitsubishi Electric: says its City Multi R2 heat recovery system is “the only 2-pipe heat recovery solution on the market”. That is the maker’s own claim. The same page says “can achieve up to 30% energy savings over conventional systems”, and elsewhere “up to 30% energy savings compared to heat pump systems”; the two statements use different comparisons and no test conditions are given.

Treat those percentages as claims, not savings you will get.

How big does VRF go?

Mitsubishi Electric UK lists City Multi YXM R2 outdoor unit bands of 22 to 45 kW, 50 to 67 kW, 73.5 to 100 kW and 106 to 112 kW, and says they use “Lower GWP R32 Refrigerant”. That is one maker’s range. Daikin’s VRV page gives no capacity range and says only “The widest range of indoor units available”. Neither page is a guide to what your building needs: that comes from a heat load calculation.

Where does VRF suit, and where does it not?

Designing Buildings says VRF suits buildings with many spaces, “such as hotels, where some rooms may be unoccupied whilst others have a very high thermal demand”, and that “They may be less suited to large uniform spaces such as gymnasiums or theatres.” Daikin’s hotel page offers VRV with “Control your units centrally or individually”. See hotel room air conditioning units, office air conditioning and fan coil units, which are the chilled-water alternative.

Like a split, VRF recirculates air; fresh air for a workplace has to come from windows or a ventilation system. Regulation 6 of the Workplace (Health, Safety and Welfare) Regulations 1992 (England, Wales and Scotland) requires ventilation “by a sufficient quantity of fresh or purified air”.

What about refrigerant in a VRF system?

The charge sits in the pipework serving every zone, and the rules count refrigerant by CO2 equivalent. This is general information, not legal advice, and covers Great Britain; Northern Ireland follows the EU F-gas system.

Tonnes CO2e = charge in kg x GWP / 1,000. The GWP of R32 is 675 (Annex I of the F-gas Regulation as it applies in Great Britain: “HFC-32 difluoromethane CH2F2 675”). The US EPA’s table gives 2,088 for R410A, labelled “Calculated”; we use it here for illustration only, as we did not check the figure the GB F-gas Regulation uses for this blend, so ask your engineer for the system’s CO2 equivalent. The leak-check steps, in the words of our rules data: leak checks are required from 5 tonnes CO2 equivalent: at least every 12 months, or 24 with a leak detection system; every 6 months from 50 tonnes, or 12 with one. Equipment of 500 tonnes or more must have a leak detection system and is then checked at least every 6 months.

Our arithmetic: the charge at which each step starts.

Step R32 (GWP 675) R410A (GWP 2,088)
5 tonnes CO2e 7.41 kg 2.39 kg
50 tonnes CO2e 74.07 kg 23.95 kg
500 tonnes CO2e 740.74 kg 239.46 kg

No maker we opened gives a typical VRF charge, so we do not give an example. Read the charge from the outdoor unit’s rating plate or the commissioning sheet, multiply by the GWP and divide by 1,000. GOV.UK says a leak must be repaired “as soon as possible” and the test repeated “within a month”. Installing, servicing and leak checking need qualified technicians working for a certified company. See F-gas rules.

What does VRF cost?

We found no published installed price for VRF on 25 November 2026, and we will not give a typical figure. Designing Buildings says three-pipe heat recovery has a greater capital cost than two-pipe. The price depends on the capacity, the number and type of indoor units, pipe runs, the outdoor unit’s location and access, controls, the electrical supply, commissioning and any ventilation. See commercial air conditioning installation. VAT on a business installation is 20% by our reading of HMRC’s notice.

For running costs, no single published input figure applies to a building: electricity used (kWh) = cooling delivered (kWh) divided by the system’s seasonal efficiency. Ask the designer for both figures. The domestic price cap does not apply to businesses; use the unit rate on your own bill.

Maintenance, records and inspection

Operators must keep records, including the quantity and type of F gas, quantities added or recovered, and the dates and results of leak checks, “for at least five years” (Article 6(2) of the F-gas Regulation as it applies in Great Britain). TM44 inspections in England and Wales apply to systems with an effective rated output of more than 12 kW; Mitsubishi’s smallest YXM R2 band starts at 22 kW, but your rating plate decides. See TM44 inspections and HVAC maintenance.

How to brief an installer

  1. Floor plans, ceiling heights, and each room’s people, equipment and hours.
  2. Which areas need heating and cooling at the same time (this decides heat pump or heat recovery).
  3. Where outdoor units and pipe routes could go, and whether your landlord and the council allow it.
  4. Electrical supply, and any existing system’s make, model and refrigerant.
  5. Ask in writing for a heat load calculation, the make, model and SEER of the units, the refrigerant type and charge, the F-gas certificate number, the competent person scheme, how fresh air is provided, what the price excludes, and warranty and servicing terms.

Frequently asked questions

What is VRF air conditioning?

It is one outdoor unit serving several indoor units, with refrigerant flow varied to suit each zone. Designing Buildings defines it as a system for heating, ventilation and air conditioning of buildings.

What is the difference between VRF and VRV?

VRV is Daikin’s trade name; Designing Buildings says VRF was first developed by Daikin as VRV. Other makers say VRF.

What is the difference between heat pump and heat recovery VRF?

Heat pump systems provide either cooling or heating to all zones; heat recovery systems can use heat from zones needing cooling to heat zones that need heating.

How many indoor units can one VRF system run?

Mitsubishi Electric UK says its City Multi VRF outdoor units “can be connected to up to 50 indoor units”. Other makers give different figures; Daikin’s page gives none.

Is VRF better than a multi split?

It is a larger system for more zones. Daikin offers central or individual control of VRV units; see multi split air conditioning for the smaller kind. We do not rank them.

Does VRF need F-gas leak checks?

Leak checks apply from 5 tonnes CO2 equivalent: about 7.4 kg of R32 or, on the US EPA figure used for illustration, 2.4 kg of R410A. Check the charge on your rating plate.

Sources

  1. Designing Buildings: Variable refrigerant flow VRF (last edited 3 August 2021) (checked 25 November 2026)
  2. Daikin UK: VRV (checked 25 November 2026)
  3. Daikin UK: Hotels (checked 25 November 2026)
  4. Mitsubishi Electric UK: City Multi VRF outdoor units (checked 25 November 2026)
  5. Mitsubishi Electric UK: City Multi YXM R2 series (checked 25 November 2026)
  6. GOV.UK: Checking F gas equipment for leaks (checked 25 November 2026)
  7. legislation.gov.uk: F-gas Regulation (EU) No 517/2014 as it applies in Great Britain, Annex I (checked 25 November 2026)
  8. US EPA: Technology Transitions GWP reference table (checked 25 November 2026)
  9. legislation.gov.uk: Workplace (Health, Safety and Welfare) Regulations 1992, regulation 6 (checked 25 November 2026)
  10. GOV.UK: Air conditioning inspections for buildings, a guide (updated 5 November 2026) (checked 25 November 2026)
  11. GOV.UK: Qualifications to work with F gas (updated 3 March 2026) (checked 25 November 2026)
  12. legislation.gov.uk: F-gas Regulation, Article 6 (records) (checked 27 November 2026)