HVAC Ductwork Explained: Types, Standards and Cleaning

By Editorial team. Updated 28 November 2026. Facts checked 25 November 2026.

Key takeaways

  • HVAC ductwork is the network of ducts that carries air between an air handling unit and the rooms of a building. It belongs to ducted and ventilation systems, not to split or cassette units, which carry refrigerant. Our commercial air conditioning guide covers both.
  • In the UK, sheet metal ductwork for commercial and industrial air systems is specified to BESA’s DW/144, which sets pressure classes A to D and leakage limits.
  • BESA says leakage testing is mandatory for high-pressure ductwork and optional for low and medium pressure. “High pressure” here is a small pressure: 2,000 Pa is about 2% of atmospheric pressure, our arithmetic.
  • Cleanliness is covered by a separate document, TR19 Air. We found no cleaning interval in the sources we opened, so we give none.
  • We found no published price for commercial ductwork. This is a design and installation job priced after a survey.

What does ductwork do?

In a mechanically ventilated commercial building, an air handling unit is typically “connected to ductwork that supplies air to and extracts air from internal spaces”, according to Designing Buildings (last edited 8 September 2026). Ducts carry supply air to rooms, return or extract air back, and fresh air in. Our pillar guide to commercial air conditioning shows where ducted systems sit among the other types, and what HVAC means explains the term.

What is the UK standard for ductwork?

BESA (the Building Engineering Services Association) published a page on sheet metal ductwork standards on 11 November 2025. It says DW/144 is “now in its third edition”, that the first edition appeared in 1998, and that it covers commercial and industrial air distribution systems “operating under normal conditions up to 70 °C”. What else it says:

  • Pressure classes. Ductwork is divided into four classes, A to D. BESA says “Class A is suitable for low-pressure systems up to 500 pascals” and “Class D applies to high-pressure systems operating up to 2,000 pascals”. The page gives no figures for classes B and C.
  • Leakage. DW/144 “provides quantitative limits for leakage at each pressure class, expressed as a function of the square root of pressure”. The page does not give the values.
  • Testing. Leakage testing is mandatory for high-pressure ductwork, “while testing remains optional for low- and medium-pressure systems”.
  • Other standards. BESA says DW/144 is harmonised with BS EN 1507 and BS EN 12237, and refers to DW/145 for dampers, fire protection components and access panels.

Our arithmetic, to put the classes in context: 500 Pa is 0.5 kPa, about 0.5% of standard atmospheric pressure (101.325 kPa), and 2,000 Pa is 2.0 kPa, about 2%. Even “high pressure” ductwork is a low pressure, which is why leakage matters more than strength.

How is ductwork kept clean?

BESA says DW/144 systems are easier to inspect and clean “in line with TR19® Air, ensuring that ductwork remains hygienic and compliant throughout its service life”. That is all its page says about TR19 Air. We did not open TR19 Air itself, so we cannot give its method or any interval. HSE’s page on improving ventilation says systems should be “maintained in line with manufacturers’ instructions”, and does not mention cleaning ductwork. Ask your maintenance contractor which cleanliness standard your contract follows: see HVAC maintenance.

How do ducted systems differ from splits and VRF?

A ducted system moves conditioned air through ducts from a central unit. A split or VRF system moves refrigerant between an outdoor unit and indoor units that sit in the rooms. Designing Buildings describes VRF as refrigerant flowing between an external condensing unit and multiple internal units, typically fan coil units. A split or cassette needs no ductwork. For the home-scale ducted type, see ducted air conditioning and ducted air conditioning cost.

Ductwork, filters and fresh air

Filters sit in the air handling unit, at the start of the duct run: see HVAC filters. HSE, quoting its Approved Code of Practice, says “recirculated air should be adequately filtered to remove impurities”, and that “Systems should therefore be designed with fresh-air inlets, which should be kept open.”

Regulation 6 of the Workplace (Health, Safety and Welfare) Regulations 1992 (England, Wales and Scotland) says “Effective and suitable provision shall be made to ensure that every enclosed workplace is ventilated” “by a sufficient quantity of fresh or purified air.” Ask the designer for the fresh air rate the system was designed to. This is general information, not legal advice; we did not check Northern Ireland.

Who designs, installs and cleans ductwork, and what does it cost?

Ductwork is designed by a building services engineer or the installer, made from the drawings, tested where the specification requires it, and cleaned by a specialist or your maintenance contractor. We found no published price for commercial ductwork installation or cleaning; any figure depends on the building, duct sizes, routes through ceiling voids and the specification. See HVAC installation for what a job involves.

How to brief a ductwork designer or installer

  1. Floor plans, ceiling void depths and any riser or plant room space.
  2. The design air volumes and fresh air rate for each room, or ask the designer to set them.
  3. Which pressure class the specification calls for, and whether leakage testing is included in the price.
  4. Where access panels and dampers go, so ducts can be inspected and cleaned.
  5. Whether insulation is part of the specification (we found no source setting a rule, so ask the designer).
  6. The cleanliness standard, handover documents and who keeps the records.

Frequently asked questions

What is HVAC ductwork?

It is the ducting that carries supply, return, fresh and extract air between an air handling unit and the rooms it serves. Designing Buildings describes the unit as connected to ductwork that supplies air to and extracts air from internal spaces.

What is DW/144?

BESA’s specification for sheet metal ductwork in commercial and industrial air systems up to 70C, now in its third edition. It sets four pressure classes and leakage limits, and BESA says testing is mandatory for high-pressure ductwork.

How often should ductwork be cleaned?

We found no interval in the sources we opened. BESA says systems should be cleaned in line with TR19 Air, which we did not read. Ask your contractor what the contract specifies and when it was last done.

Do split air conditioners need ductwork?

No. A split moves refrigerant between an outdoor and an indoor unit, so it needs pipework, not ducts. Ducted types are a separate kind of system.

Does ductwork need insulating?

We found no source that sets a rule, so we do not state one. Insulation is a design and specification matter: ask the designer.

What are ductwork pressure classes?

DW/144 groups ductwork into classes A to D. BESA says class A suits low-pressure systems up to 500 Pa and class D high-pressure systems up to 2,000 Pa. It does not give the limits for B and C.

Sources

  1. BESA: Sheet metal ductwork standards (11 November 2025) (checked 25 November 2026)
  2. Designing Buildings: HVAC (checked 25 November 2026)
  3. Designing Buildings: Variable refrigerant flow VRF (checked 25 November 2026)
  4. HSE: How to improve ventilation (checked 25 November 2026)
  5. legislation.gov.uk: Workplace (Health, Safety and Welfare) Regulations 1992, regulation 6 (checked 25 November 2026)