Key takeaways
- Four steps: measure the room, apply the rule (about 100 W per m2 at a 2.4 m ceiling), adjust for sun, loft, kitchen, conservatory and people, then choose the smallest size sold that is at or above the answer.
- A typical 4 x 3.5 m double bedroom needs 4,777 BTU (1.40 kW), so a 5,000 BTU portable or a 2.0 kW split.
- A single-hose portable cools less than its rated BTU suggests, so check the maker’s own room size and go up a size if it falls short.
- Above 24,000 BTU (7.03 kW), no single domestic unit is enough: use two units or ask an installer for a heat-load survey.
What size air conditioner do I need? Find your room’s volume, apply the rule below and round up to a size you can buy. Our BTU calculator does the sums; this page explains each step and how to choose between a portable and a split. If you want the number first, see how many BTU you need.
Step 1: measure the room
Measure length, width and average ceiling height in metres. A loft with sloping walls needs an average height. Multiply the three to get the volume in cubic metres. A 4 x 3.5 m room with a 2.4 m ceiling is 33.6 m3.
Step 2: apply the rule
Daikin UK says typical UK homes need “around 0.1 kW per square metre” for average ceiling heights and insulation, and that most sizing rules assume a 2.4 m ceiling. A 3 m ceiling adds 25% to the volume, “and so should” the cooling capacity. We scale by volume: cooling needed in watts = volume x 100 / 2.4. Then multiply watts by 3.412141 for BTU per hour.
Worked example: 33.6 m3 x 41.6667 = 1,400 W, which is 4,777 BTU, so 5,000 BTU.
Step 3: adjust for the room
Add the percentages that apply, multiply, then add 180 W for each person beyond two. Use only one of kitchen or conservatory.
| Adjustment | Figure | Source |
|---|---|---|
| Sun-facing (large south or west windows) | +15% | Daikin UK gives 10 to 20% |
| Kitchen | +20% | Daikin UK gives 10 to 20%; we take the top |
| Loft or top floor | +20% | Electric Point (a UK retailer’s guide) gives 10 to 20% |
| Conservatory or glazed garden room | +30% | Electric Point gives at least 25 to 30%; do not add sun as well |
| Poorly insulated (single glazing, uninsulated walls) | +10% | Electric Point gives 5 to 10% |
| Each person beyond two | +180 W (614 BTU) | Daikin UK: 0.18 kW a person |
The loft, conservatory and insulation figures are a common rule of thumb from one retailer’s guide, not a maker’s or an engineer’s calculation. A glass roof or a hot loft can need more. Our worked example for a sun-facing living room, 5 x 4 m with four people: 48 m3 = 2,000 W; x 1.15 = 2,300 W; + 360 W = 2,660 W = 9,076 BTU, so 10,000 BTU.
Step 4: choose the type and the size you can buy
Choose the smallest size sold that is equal to or above your answer. Electric Point’s advice is the same: always round up, never down. Portable sizes are 5,000, 7,000, 8,000, 9,000, 10,000, 12,000, 14,000, 15,000, 16,000, 18,000, 20,000 and 24,000 BTU.
Portable
Single-hose portables are rated in a way that flatters them. Under the GB energy label rules, a single-duct unit’s condenser is not supplied with outdoor air but with indoor air. The US Department of Energy found that warm air leaking in to replace the air a portable blows out makes real cooling lower than the older rating, and set a revised rating that subtracts it. No UK or EU document gives a percentage, so we apply none. Instead, show the maker’s own room size beside ours, and if the maker’s figure does not cover your room, go up a size. A split avoids most of the problem; a dual-hose unit would too, but when we checked on 14 November 2026 we found no dual hose portable confirmed by its maker on UK sale. See portable air conditioners.
Split
Splits are sold in kW, not BTU: 2.0, 2.5, 3.5 and 5.0 kW are common, and an installer sizes one. Our rule: choose the smallest split kW at or above the computed need in kW.
| Computed need | Nearest size to buy | Split size |
|---|---|---|
| 5,000 BTU = 1.47 kW | 5,000 BTU | 2.0 kW (6,824 BTU) |
| 7,000 BTU = 2.05 kW | 7,000 BTU | 2.5 kW (8,530 BTU) |
| 10,000 BTU = 2.93 kW | 10,000 BTU | 3.5 kW (11,942 BTU) |
| 12,000 BTU = 3.52 kW | 12,000 BTU | 3.5 kW only if the computed need is at or below 11,942 BTU, otherwise 5.0 kW |
See split air conditioners and, for fitting, installation cost. For several rooms, see multi-split systems.
Answers for typical UK rooms
| Room | Working | Need | Portable size | Split size |
|---|---|---|---|---|
| Bedroom 4 x 3.5 m, two people | 33.6 m3 = 1,400 W | 4,777 BTU (1.40 kW) | 5,000 | 2.0 kW |
| Living room 5 x 4 m, sun-facing, four people | 2,660 W | 9,076 BTU (2.66 kW) | 10,000 | 3.5 kW |
| Loft bedroom 4 x 4 m, sun-facing | 1,600 W x 1.35 = 2,160 W | 7,370 BTU (2.16 kW) | 8,000 | 2.5 kW |
| Kitchen 4 x 3 m | 1,200 W x 1.2 = 1,440 W | 4,913 BTU (1.44 kW) | 5,000 | 2.0 kW |
| Conservatory 4 x 3.5 m, 2.5 m ceiling | 1,458 W x 1.3 = 1,896 W | 6,469 BTU (1.90 kW) | 7,000 | 2.0 kW |
| Open-plan 6 x 5 m, poorly insulated, three people | 3,300 W + 180 W = 3,480 W | 11,874 BTU (3.48 kW) | 12,000 | 3.5 kW |
The loft example uses +15% sun and +20% loft, which is x 1.35. Try your own room in the room size calculator. For bedroom picks, see air conditioners for a bedroom; for single sizes, see 9,000 BTU and 12,000 BTU.
Too big or too small: what goes wrong
A unit that is too small cannot keep up with the heat, so the room stays warm in a heatwave. A unit that is too big costs more to buy and, for the same type, draws more power at full output. We make no wider claims, because we found no sourced UK figure on humidity or cycling. A bigger unit is not automatically better: the rule above already adds a margin for sun, people and heat sources.
When to ask an installer for a heat-load calculation
Ask for one if your need is above 24,000 BTU (7.03 kW), if the space is open-plan across several floors, if you have a glass roof or a heavily glazed room, or if you are cooling several rooms with one system. Daikin’s guide notes that most sizing rules are for an average home; an installer’s survey is a full calculation of your own.
Frequently asked questions
What size air conditioner do I need for a bedroom?
A 4 x 3.5 m double bedroom at 2.4 m needs 4,777 BTU, so a 5,000 BTU portable or a 2.0 kW split. Under the roof or sun-facing, it can need 7,000 to 8,000 BTU.
What size air conditioner for a 20 m2 room?
At a 2.4 m ceiling, 20 m2 is 48 m3, which needs 6,824 BTU (2.00 kW), so 7,000 BTU. Sun-facing it is 7,848 BTU, so 8,000 BTU.
What kW air conditioner do I need?
Divide the BTU you need by 3,412.141. A plain 20 m2 room needs 2.00 kW. Then choose the smallest split kW at or above that, such as 2.5 kW.
Is it better to oversize an air conditioner?
Not as a rule. Round up to the next size sold, then stop. A larger unit costs more to buy and has a higher rated power.
Do I need a different size for a portable?
Check the maker’s room size. Single-hose portables are rated in a way that flatters them, so if the maker’s figure is below ours, trust the maker’s and go up a size.
Can one air conditioner cool a whole house?
Not usually. Above 24,000 BTU no single domestic unit covers the load. Use several units or a multi-split, and ask an installer to survey it.
Sources
- Daikin UK: air conditioner size guide (checked 14 November 2026)
- Electric Point: portable air conditioning units UK buying guide (checked 14 November 2026)
- legislation.gov.uk: Regulation (EU) No 626/2011, Annex VII (checked 14 November 2026)
- Federal Register: DOE test procedures for portable air conditioners, 1 June 2016 (checked 14 November 2026)
- NIST: SP 811, Appendix B.9, conversion factors (checked 14 November 2026)