Key takeaways
- The air conditioning noise regulations UK councils apply work in two stages: a planning noise test before the unit goes in, and the statutory nuisance rules once it is running.
- Before: in England and Wales, a unit fitted under permitted development must pass the MCS 020 a) calculation, a limit of 37 dB LAeq,5mins at each nearby assessment position, such as a neighbour’s bedroom window.
- After: there is no fixed decibel limit, but noise that unreasonably and substantially interferes with a neighbour’s home, or harms health, can be a statutory nuisance. The council must investigate and, if it finds one, serve an abatement notice.
- Northern Ireland has its own Act with the same “prejudicial to health or a nuisance” test, and still has a 1 metre boundary rule for heat pumps.
- Older pages quote 42 dB from the earlier standard. The current figure is 37 dB.
This is general information, not legal advice.
Is there a legal noise limit for air conditioning?
Not once it is installed. The only decibel figure is a planning one (our guide to air conditioning planning permission covers the other planning limits): the 37 dB limit in MCS 020 a), which an outdoor unit must meet to go up without a planning application. After that, the law on noise from a neighbour’s unit has no decibel figure: the test is whether the noise is a nuisance or harms health.
This page covers fixed systems with an outdoor unit, such as a split air conditioner or an air-to-air heat pump. A portable unit indoors is not covered by the planning noise test, though the nuisance rules apply to any noise from premises.
Before it is fitted: the MCS 020 a) noise calculation
Noise is checked on paper before anything goes on the wall. In England and Wales, a heat-and-cool unit fitted without a planning application has to pass a sound calculation as one of its permitted development conditions; a cooling-only unit is not covered by that route and needs a planning application.
MCS 020 a) Issue 1.1, dated 14 April 2025, “sets out the sound calculation which must be conducted for domestic installations of heat pumps to be ‘permitted development’”. It checks whether “the permitted development noise limit of 37 dB LAeq,5mins” would be met at each assessment position. The Planning Portal says the installation must comply with MCS 020a, and the Welsh Government’s rules (updated 1 June 2026) name MCS 020(a) too.
What it checks
- Assessment positions. A point 1 metre outside the middle of any door or window to a habitable room (a bedroom or living room, not a bathroom, hallway or utility room) of a neighbouring home. Where the unit is on a block of flats, other flats in the same block count as neighbouring property.
- Every side. The installer fills in one table for each assessment position that could be affected, on all sides of the property and on each floor. The closest window is not always the loudest one.
- One or two units. There is one table for one heat pump and another for two, where the levels from both are added together.
- The result. If the calculated level at every assessment position is 37.0 dB(A) or lower, the unit meets the noise limit. If not, it is not permitted development.
The installer keeps one copy of the completed table and gives you another. Passing it is not enough on its own: MCS 020 a) says compliance “does not bestow permitted development rights”, because every other limit still applies. It also warns that an installation which does not meet the standard “may be subject to enforcement action by the local planning authority”.
How the numbers work
MCS 020 a) works out the sound level at the window from four things: the unit’s sound power level from the maker’s data (not its “low noise mode” figure), how many reflecting surfaces are within 1 metre of it, the distance to the window, and any wall or fence in the way. A solid brick wall that hides the window completely takes off 10 dB; one that leaves a partial view takes off 5 dB. Open fences and hedges count for nothing.
Here is what that means, starting from the worked example in MCS 020 a) itself: a unit with a sound power level of 60 dB(A), standing on the ground against one wall. We ran the standard’s own formula for the other rows.
| Distance to the neighbour’s window | Wall or fence in the way | Level at the window | Passes 37 dB? |
|---|---|---|---|
| 8.0 m | Brick wall, partial view (minus 5 dB) | 32.0 dB(A) (the MCS example) | Yes |
| 8.0 m | None, full view | 37.0 dB(A) | Yes, just |
| 5.0 m | None, full view | 41.1 dB(A) | No |
| 8.0 m, unit in a corner between two walls | None, full view | 40.0 dB(A) | No |
The working, in plain words: the level falls by about 6 dB each time the distance doubles; each extra reflecting surface close to the unit adds about 3 dB; a solid barrier takes off up to 10 dB. MCS 020 a) says a unit with more than three reflecting surfaces, such as one in a small lightwell, will not meet the standard. These rows are illustrations of the method for a 60 dB(A) unit, not figures for any particular model.
Northern Ireland: the 1 metre boundary rule
Northern Ireland’s permitted development right for heat pumps (Class G, in force since 4 July 2023) says no part of the unit may be “within 1 metre of the curtilage boundary of another dwelling house”. England dropped its boundary rule on 29 May 2025, so this is now a Northern Ireland rule only.
Northern Ireland’s Order defines its noise standard as MCS 020 Issue 1.3, dated 19 June 2019, not the 2025 MCS 020 a). We have not read that issue, so we give no noise figure for Northern Ireland: ask your installer which calculation they use.
After it is fitted: statutory nuisance
Once a unit is running, the law that matters is statutory nuisance. Section 79(1)(g) of the Environmental Protection Act 1990 lists “noise emitted from premises so as to be prejudicial to health or a nuisance”. There are versions for England and Wales and for Scotland, with the same wording. In Northern Ireland, section 63(1)(i) of the Clean Neighbourhoods and Environment Act (Northern Ireland) 2011 uses the same words, and says “noise” includes vibration.
What counts
GOV.UK’s guidance for England says that to count as a statutory nuisance, the problem must either:
- “unreasonably and substantially interfere with the use or enjoyment of a home or other premises”; or
- “injure health or be likely to injure health”.
There is no decibel threshold in either test. A unit that passed the 37 dB calculation can still be a nuisance if, for example, it runs through the night next to a bedroom window or rattles on its brackets.
What the council does
- Investigates. Under section 79, a council must take “such steps as are reasonably practicable to investigate the complaint” from someone living in its area. GOV.UK says councils “must investigate complaints”.
- Serves an abatement notice. If the council agrees a nuisance is happening, has happened or will happen, it “must serve an abatement notice (usually on the person responsible)”. The notice can require the person “to stop the activity or limit it to certain times”, and can include specific actions to reduce the problem. For noise, GOV.UK says the notice “can be delayed for up to 7 days” while the council tries to get the noise stopped or restricted.
- Appeals. The person served can appeal to a magistrates’ court “within 21 days of getting the notice”.
- Penalties. Breaking a notice can mean a fine and further fines for each day it continues, both set by the court. The council can also do the work itself and recover the cost.
How to keep a unit quiet
The same things that pass the MCS 020 a) calculation keep neighbours happy afterwards:
- Distance. Put the outdoor unit as far as practical from neighbours’ bedroom and living room windows.
- Screening. A solid, gap-free masonry wall or a fence at least 18 mm thick, extending at least 1 metre beyond each side of the unit, cuts the level the most.
- Fewer reflecting surfaces. Avoid tucking the unit into a corner or a narrow passage.
- A quieter unit. Compare sound power levels on makers’ specification sheets before you buy.
- Upkeep. A rattle or a new noise is a fault to fix. Our guides to air conditioning servicing and air conditioning repair cover what an engineer checks.
If you are the neighbour: what to do first
- Talk to them. GOV.UK’s advice on neighbour disputes is to “Try to solve the problem informally by talking to them.” Many people do not know how their unit sounds next door.
- Try mediation if talking does not work.
- Complain to the council’s environmental health team. Keep a note of when the noise happens and how it affects you. The council will investigate, and if it finds a statutory nuisance it must serve an abatement notice.
If the unit was put up recently, the council’s planning team can also check whether it needed planning permission.
What to do next
- Fitting a unit: ask your installer for the completed MCS 020 a) table for every assessment position, and keep your copy.
- In Northern Ireland, check the unit is at least 1 metre from the neighbour’s boundary.
- Disturbed by a neighbour’s unit: talk to them first, then contact the council’s environmental health team.
- If you are in a flat, see our guide to air conditioning in a leasehold flat, because the freeholder may also have a say.
Frequently asked questions
What is the noise limit for air conditioning units in the UK?
There is no fixed limit once a unit is installed. Before installation, a unit fitted under permitted development in England and Wales must pass the MCS 020 a) calculation of 37 dB LAeq,5mins at each neighbour’s assessment position.
Can my neighbour complain about my air conditioning unit?
Yes. Noise that unreasonably and substantially interferes with the use or enjoyment of their home, or harms health, can be a statutory nuisance, and the council must investigate a complaint.
How close to my neighbour can an air conditioning unit be?
England has had no boundary distance since 29 May 2025, and the Welsh rules we read state none; the MCS 020 a) noise calculation decides. In Northern Ireland the unit must be at least 1 metre from the boundary of a neighbouring house.
What can I do about a noisy air conditioning unit next door?
Talk to your neighbour first, then try mediation. If that fails, complain to the council’s environmental health team, which must investigate and can serve an abatement notice.
Is 42 dB still the heat pump noise limit?
No. The current standard, MCS 020 a) Issue 1.1 of 14 April 2025, uses 37 dB LAeq,5mins. The 42 dB figure comes from the earlier version and still appears on older pages.
Can the council make me remove an air conditioning unit?
It can require you to stop or limit the noise. An abatement notice can require the activity to stop or be limited to certain times, and a unit that needed planning permission and did not have it may face planning enforcement. The sources we read do not say a council will order removal in every case.
This is general information, not legal advice.
Sources
- MCS: MCS 020 a) Issue 1.1, sound calculation for permitted development, 14 April 2025 (PDF) (checked 14 November 2026)
- Planning Portal: Air source heat pump permitted development (England) (checked 14 November 2026)
- Welsh Government: Planning permission, heat pumps (rules updated 1 June 2026) (checked 14 November 2026)
- legislation.gov.uk: Planning (General Permitted Development) (Amendment) Order (Northern Ireland) 2023, Schedule, Class G (checked 14 November 2026)
- legislation.gov.uk: Environmental Protection Act 1990, section 79 (checked 14 November 2026)
- GOV.UK: Statutory nuisances, how councils deal with complaints (England, published 7 April 2015) (checked 14 November 2026)
- legislation.gov.uk: Clean Neighbourhoods and Environment Act (Northern Ireland) 2011, section 63 (checked 14 November 2026)
- GOV.UK: How to resolve neighbour disputes (checked 14 November 2026)